Mircom FA-1000 SERIES User Manual

Browse online or download User Manual for Security access control systems Mircom FA-1000 SERIES. fire alarm control panels fa-1000 series

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
FIRE ALARM CONTROL PANELS FA-1000 SERIES
Description
Mircom’s FA-1000 Series Microprocessor Based Fire
Alarm Control Panels are Multi-Zone units designed
for maximum exibility and easy installation and
operation. Fully congurable from the front panel
using push buttons and DIP switches, the FA-1000
Series enables the user to congure the system
to meet their specic requirements. With a large
capacity of supervised Class A (Style D) or Class
B (Style B) Initiating Circuits and supervised Class
A (Style Z) or Class B (Style Y) Indicating Circuits,
the FA-1000 Series is designed to meet virtually all
applications.
The FA-1000 Series consists of a Main Fire Alarm
Chassis which houses and controls all other
modules. Additional modules may be installed to
congure the system to meet any requirements that
the user may have. The FA-1000 Series allows for
additional Indicating Circuit, Initiating Circuit and
Relay modules to be added to the system. In addition
it allows for optional modules such as the UDACT-
300A Digital Communicator and the PR-300 Polarity
Reversal / City Tie Module.
Equipped with Conguration DIP Switches on the
Main Display Module the FA-1000 Series Fire Alarm
Control Panels are congured through a combination
of DIP switch and button settings. Through this
conguration method the user can dene the system
as a Single Stage or Two Stage operation as well
as perform various functions such as a One Man
Walk Test.
Features
Large system capacity
Modular design
Each Indicating Circuit can be congured as
Silenceable or Non-Silenceable
Audibles may be congured as Steady, Temporal
Code, California Code or March Time
Each Initiating Circuit can be configured as
Alarm, Supervisory, Waterow or Trouble
Two LEDs per Initiating circuit; one for Trouble
and one for Status
Initiating and Indicating Circuits may be
individually disconnected by a DIP switch
Congurable Signal Silence Inhibit, Auto Signal
Silence, Two-Stage Operation and One Man
Walk Test
Subsequent Alarm, Supervisory and Trouble
operation
Two outputs for 4 wire resettable smoke power
supply (200 mA Max. each)
Auxiliary relay contacts for Common Alarm and
Common Supervisory as well as a Common
Trouble Relay (Each relay contact Form C, 28
VDC @ 1 Amp (resistive))
RS-485 Interface for RA-1000 Remote Multiplex
Annunciators
Interface for Remote Trouble Indicator
Easy conguration via push buttons and DIP
switches on the front panel
Fully site or field programmable Indicating
Circuits and Auxiliary Relays
Extensive Transient Protection
Slide-in labels for zone identication
6 Amp or 12 Amp power supplies available
Removable door for easy installation and
servicing
Removable terminal blocks for easy wiring and
servicing
Optional Modules
UDACT-300A Digital Communicator Module
Polarity Reversal and City Tie Module
Two sizes of Surface mounted cabinets
Semi-Flush mounting available with use of
optional trim rings
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specications and models and also to discontinue models.
5620
NOT TO BE USED FOR INSTALLATION PURPOSES.
S7010 S7010
MEA
approved
7135-1477:106
313-97-E
CATALOG NUMBER
Page view 0
1 2 3 4

Summary of Contents

Page 1 - CATALOG NUMBER

FIRE ALARM CONTROL PANELS FA-1000 SERIESDescriptionMircom’s FA-1000 Series Microprocessor Based Fire Alarm Control Panels are Multi-Zone units design

Page 2 - CAT. 5620

MCC-1024-6AMain Chassis comes complete with 8 Class B (Style B) or 4 Class A (Style D) Initiating Circuits, 4 Class A/B (Style Z/Y) Indicating circuit

Page 3

BB-1024 EnclosureThis enclosure is capable of handling one MCC-1024-6A or MCC-1024-12A Main Chassis and up to 17 AH Batteries. The FA-UN

Page 4 - Electrical Requirements

SpecicationsElectrical RequirementsMCC-1024-6APrimary Input Power: 120 volts, 60 Hz, 2 Amps maximum Indicating Current: 24VDC unltered, 5 Amps maxim

Comments to this Manuals