FA-262
Fire Alarm Control Panel
LT-2015MIR Rev. 1
Frbruary 2008
Installation and Operator’s Manual
Advanced Life Safety Solutions Advanced Life Safety Solutions
U.S.A.
60 Industrial Parkway
Cheektowaga, NY 14227
Tel: 1-888-660-4655 Fax: 1-888-660-4113
Page view 0
1 2 3 4 5 6 ... 51 52

Summary of Contents

Page 1 - Fire Alarm Control Panel

Canada 25 Interchange Way Vaughan, ON L4K 5W3 Tel: 905-660-4655 Fax: 905-660-4113  Mircom 2002Printed in CanadaSubject to change without prior notice

Page 2

FA-262 Installation & Operator’s Manual42.3 FA-262 OverviewZone Label InsertA zone label insert is installed in the zone window area. Reach behind

Page 3 - Table of Contents

FA-262 Installation & Operator’s Manual52.4 Planning Your InstallationAs a minimum, the following points should be considered to ensure that the i

Page 4

FA-262 Installation & Operator’s Manual62.6 Module Current Ratings2.7 Standby Battery calculation chartAll components that draw current from the p

Page 5 - List of Figures

FA-262 Installation & Operator’s Manual72.8 Calculation for Standby Battery RequirementStep DeviceCurrent per device (mA)Number of deviceTotal Sta

Page 6

FA-262 Installation & Operator’s Manual83.0 Installing the FA-262 Fire Panel3.1 Environmental SpecificationsConsider the following conditions when

Page 7 - 1.0 Introduction

FA-262 Installation & Operator’s Manual93.3 Mounting the FA-262Figure 6: Mounting DimensionsFigure 7: Knockout LocationsDimensions in inches

Page 8 - 1.6 Battery Maintenance

FA-262 Installation & Operator’s Manual104.0 Wiring the FA-2624.1 Wiring SpecificationsFigure 8: FA-262 Terminal DescriptionsTerminal LabelDescrip

Page 9 - Fire Panel

FA-262 Installation & Operator’s Manual11Figure 9: Connecting 2-Wire Alarm Initiating DevicesTypical1. Maximum 30 smoke detectors per zone (100 µA

Page 10

FA-262 Installation & Operator’s Manual12Figure 10: Connecting 4-Wire Smoke Detectors1. Program as zone type 01, instant alarm.2. Maximum total lo

Page 11 - 2.5 Electrical Specifications

FA-262 Installation & Operator’s Manual13NAC Wiring ChartFigure 13: Connecting BatteriesFigure 14: Connecting AC PowerMaximum Total Loop(ohms) Max

Page 13

FA-262 Installation & Operator’s Manual14Figure 15: Connecting the Alarm and Trouble RelaysFigure 16: Connecting Optional DevicesSee installation

Page 14 - Primary AC

FA-262 Installation & Operator’s Manual15To calculate the wire run distance for any gauge wire and any maximum current value, use the following fo

Page 15 - Figure 7: Knockout Locations

FA-262 Installation & Operator’s Manual165.0 Panel Operation5.1 Operating SequencesThis section describes how the panel functions under various co

Page 16 - 4.0 Wiring the FA-262

FA-262 Installation & Operator’s Manual175.4 Supervisory Zone AlarmsWhen an alarm occurs on a supervisory zone (type 04), the corresponding zone s

Page 17 - DC, 2 Amps max

FA-262 Installation & Operator’s Manual18System TroublesSystem faultsCommon Trouble LEDBuzzerTrouble RelayOther IndicatorsAlarm zone open circuit

Page 18

FA-262 Installation & Operator’s Manual195.6 System Reset OperationTo reset the system, press the ‘Reset System’ button. The panel will remove all

Page 19 - C22.1, Part 1, Section 32

FA-262 Installation & Operator’s Manual205.8 Walk Test (Installer function only)To do a walk test, all zone alarms, troubles and relays must be in

Page 20

FA-262 Installation & Operator’s Manual215.9 NAC operationSee also “NAC Temporal/Steady Programming - Section 1 (‘NAC1’ LED on steady)” on page 25

Page 21

FA-262 Installation & Operator’s Manual226.0 Programming the FA-265 System6.1 How to Program the FA-265You can program the panel using the control

Page 22 - 5.0 Panel Operation

FA-262 Installation & Operator’s Manual23When you first enter programming mode, the panel will be at zone programming (section 0). Each programmin

Page 23 - 5.5 Trouble Operation

FA-262 Installation & Operator’s ManualiTable of Contents1.0 Introduction ...

Page 24

FA-262 Installation & Operator’s Manual246.2 Programming Section DescriptionsZone Programming (Section 0)In this zone programming section, the pan

Page 25 - 5.7 Lamp Test

FA-262 Installation & Operator’s Manual25NAC Temporal/Steady Programming - Section 1 (‘NAC1’ LED on steady)You can individually program both NAC1

Page 26

FA-262 Installation & Operator’s Manual26Silence Inhibit and Walk Test Programming - Section 3 (‘Battery’ LED on steady)Signal Silence Inhibit Tim

Page 27 - 5.10 Relay Function

FA-262 Installation & Operator’s Manual276.3 Viewing the Event Buffer1. Enter the programming mode by pressing and holding the Walk Test switch fo

Page 28 - FA-265 System

FA-262 Installation & Operator’s Manual28Event Buffer TableDisplay EventSteady Common Alarm LED Null EventFlashing Zone X Alarm LED Verified Zone

Page 29

FA-262 Installation & Operator’s Manual297.0 Startup of the FA-2657.1 Prior to power up•Verify that all field wiring is free of shorts, opens and

Page 30

FA-262 Installation & Operator’s Manual308.0 Programming Worksheets8.1 Entering Programming ModePlease see “6.0 Programming the FA-265 System” on

Page 31

FA-262 Installation & Operator’s Manual318.2 Zone Programming (Section 0)Program each of the zones as one of the following types. (See “Zone Progr

Page 32

FA-262 Installation & Operator’s Manual328.5 Silence Inhibit and Walk Test Programming (Section 3)Please see “Silence Inhibit and Walk Test Progra

Page 33 - 6.3 Viewing the Event Buffer

FA-262 Installation & Operator’s Manual339.0 Appendix: Table of Compatible Smoke DetectorsPanel CIDMax. # DetectorsManufacturerModelModelCIDBaseBa

Page 34

FA-262 Installation & Operator’s Manualii9.0 Appendix: Table of Compatible Smoke Detectors ...

Page 35 - 7.0 Startup of the FA-265

FA-262 Installation & Operator’s Manual3401 25System Sensor2112/24T A N/A N/APhotoelectric, 12/24VDC, terminal strip01 25System Sensor4451HT4451HT

Page 36 - 8.0 Programming Worksheets

FA-262 Installation & Operator’s Manual359.1 Smoke Detector Bases9.2 Compatible 4-Wire Smoke DetectorsMax. # DetectorsManufacturerModelBaseCIDDesc

Page 37 -  *Bell 

FA-262 Installation & Operator’s Manual369.3 Compatible Horns/StrobesSystem Sensor Type CdVoltage (FWR)P2415(W)(A) H/S 15 20-30P241575(W)(A) H/S 1

Page 38 -  50Hz 

FA-262 Installation & Operator’s Manual37Wheelock Type CdVoltage (FWR)NS-2415W-FR(W) H/S 15 20-31NS-241575W-FR(W) H/S 15/75 20-31NS-2430W-FR(W) H/

Page 39

FA-262 Installation & Operator’s Manual38FCC Compliance StatementCAUTION: Changes or modifications not expressly approved by the manufacturer coul

Page 40

FA-262 Installation & Operator’s Manual39Warranty & Warning InformationWarning Please Read Carefully Note to End Users: This equipment is subj

Page 41 - 9.1 Smoke Detector Bases

FA-262 Installation & Operator’s Manual40reasons, such as: the smoke detectors or heat detector may have been improperly installed or positioned;

Page 42 - 9.3 Compatible Horns/Strobes

FA-262 Installation & Operator’s Manual41Limited Warranty Mircom Technologies Ltd. warrants the original purchaser that for a period of two years

Page 43

FA-262 Installation & Operator’s Manual42Out of Warranty Repairs Mircom Technologies Ltd. will at its option repair or replace out-of-warranty pro

Page 45

FA-262 Installation & Operator’s ManualiiiList of FiguresFigure 1: FA-262 cabinet with door closed ...

Page 48 - Out of Warranty Repairs

Canada25 Interchange WayVaughan, ON L4K 5W3Tel: 905-660-4655 Fax: 905-660-4113© Mircom 2007Printed in CanadaSubject to change without prior noticewww.

Page 50

FA-262 Installation & Operator’s Manual11.0 Introduction1.1 The FA-262 Fire Alarm Control UnitGeneral features•Two initiating device circuits, cla

Page 51

FA-262 Installation & Operator’s Manual21.3 Technical Support and General InformationFor technical support call 1-888-660-4655, or email techsuppo

Page 52 - Printed in Canada

FA-262 Installation & Operator’s Manual32.0 Preparing to Install the FA-262 Fire Panel2.1 Unpacking the FA-262The basic FA-262 package includes th