FA-262 Installation & Operator’s Manual42.3 FA-262 OverviewZone Label InsertA zone label insert is installed in the zone window area. Reach behind
FA-262 Installation & Operator’s Manual52.4 Planning Your InstallationAs a minimum, the following points should be considered to ensure that the i
FA-262 Installation & Operator’s Manual62.6 Module Current Ratings2.7 Standby Battery calculation chartAll components that draw current from the p
FA-262 Installation & Operator’s Manual72.8 Calculation for Standby Battery RequirementStep DeviceCurrent per device (mA)Number of deviceTotal Sta
FA-262 Installation & Operator’s Manual83.0 Installing the FA-262 Fire Panel3.1 Environmental SpecificationsConsider the following conditions when
FA-262 Installation & Operator’s Manual93.3 Mounting the FA-262Figure 6: Mounting DimensionsFigure 7: Knockout LocationsDimensions in inches
FA-262 Installation & Operator’s Manual104.0 Wiring the FA-2624.1 Wiring SpecificationsFigure 8: FA-262 Terminal DescriptionsTerminal LabelDescrip
FA-262 Installation & Operator’s Manual11Figure 9: Connecting 2-Wire Alarm Initiating DevicesTypical1. Maximum 30 smoke detectors per zone (100 µA
FA-262 Installation & Operator’s Manual12Figure 10: Connecting 4-Wire Smoke Detectors1. Program as zone type 01, instant alarm.2. Maximum total lo
FA-262 Installation & Operator’s Manual13NAC Wiring ChartFigure 13: Connecting BatteriesFigure 14: Connecting AC PowerMaximum Total Loop(ohms) Max
FA-262 Installation & Operator’s Manual14Figure 15: Connecting the Alarm and Trouble RelaysFigure 16: Connecting Optional DevicesSee installation
FA-262 Installation & Operator’s Manual15To calculate the wire run distance for any gauge wire and any maximum current value, use the following fo
FA-262 Installation & Operator’s Manual165.0 Panel Operation5.1 Operating SequencesThis section describes how the panel functions under various co
FA-262 Installation & Operator’s Manual175.4 Supervisory Zone AlarmsWhen an alarm occurs on a supervisory zone (type 04), the corresponding zone s
FA-262 Installation & Operator’s Manual18System TroublesSystem faultsCommon Trouble LEDBuzzerTrouble RelayOther IndicatorsAlarm zone open circuit
FA-262 Installation & Operator’s Manual195.6 System Reset OperationTo reset the system, press the ‘Reset System’ button. The panel will remove all
FA-262 Installation & Operator’s Manual205.8 Walk Test (Installer function only)To do a walk test, all zone alarms, troubles and relays must be in
FA-262 Installation & Operator’s Manual215.9 NAC operationSee also “NAC Temporal/Steady Programming - Section 1 (‘NAC1’ LED on steady)” on page 25
FA-262 Installation & Operator’s Manual226.0 Programming the FA-265 System6.1 How to Program the FA-265You can program the panel using the control
FA-262 Installation & Operator’s Manual23When you first enter programming mode, the panel will be at zone programming (section 0). Each programmin
FA-262 Installation & Operator’s ManualiTable of Contents1.0 Introduction ...
FA-262 Installation & Operator’s Manual246.2 Programming Section DescriptionsZone Programming (Section 0)In this zone programming section, the pan
FA-262 Installation & Operator’s Manual25NAC Temporal/Steady Programming - Section 1 (‘NAC1’ LED on steady)You can individually program both NAC1
FA-262 Installation & Operator’s Manual26Silence Inhibit and Walk Test Programming - Section 3 (‘Battery’ LED on steady)Signal Silence Inhibit Tim
FA-262 Installation & Operator’s Manual276.3 Viewing the Event Buffer1. Enter the programming mode by pressing and holding the Walk Test switch fo
FA-262 Installation & Operator’s Manual28Event Buffer TableDisplay EventSteady Common Alarm LED Null EventFlashing Zone X Alarm LED Verified Zone
FA-262 Installation & Operator’s Manual297.0 Startup of the FA-2657.1 Prior to power up•Verify that all field wiring is free of shorts, opens and
FA-262 Installation & Operator’s Manual308.0 Programming Worksheets8.1 Entering Programming ModePlease see “6.0 Programming the FA-265 System” on
FA-262 Installation & Operator’s Manual318.2 Zone Programming (Section 0)Program each of the zones as one of the following types. (See “Zone Progr
FA-262 Installation & Operator’s Manual328.5 Silence Inhibit and Walk Test Programming (Section 3)Please see “Silence Inhibit and Walk Test Progra
FA-262 Installation & Operator’s Manual339.0 Appendix: Table of Compatible Smoke DetectorsPanel CIDMax. # DetectorsManufacturerModelModelCIDBaseBa
FA-262 Installation & Operator’s Manualii9.0 Appendix: Table of Compatible Smoke Detectors ...
FA-262 Installation & Operator’s Manual3401 25System Sensor2112/24T A N/A N/APhotoelectric, 12/24VDC, terminal strip01 25System Sensor4451HT4451HT
FA-262 Installation & Operator’s Manual359.1 Smoke Detector Bases9.2 Compatible 4-Wire Smoke DetectorsMax. # DetectorsManufacturerModelBaseCIDDesc
FA-262 Installation & Operator’s Manual369.3 Compatible Horns/StrobesSystem Sensor Type CdVoltage (FWR)P2415(W)(A) H/S 15 20-30P241575(W)(A) H/S 1
FA-262 Installation & Operator’s Manual37Wheelock Type CdVoltage (FWR)NS-2415W-FR(W) H/S 15 20-31NS-241575W-FR(W) H/S 15/75 20-31NS-2430W-FR(W) H/
FA-262 Installation & Operator’s Manual38FCC Compliance StatementCAUTION: Changes or modifications not expressly approved by the manufacturer coul
FA-262 Installation & Operator’s Manual39Warranty & Warning InformationWarning Please Read Carefully Note to End Users: This equipment is subj
FA-262 Installation & Operator’s Manual40reasons, such as: the smoke detectors or heat detector may have been improperly installed or positioned;
FA-262 Installation & Operator’s Manual41Limited Warranty Mircom Technologies Ltd. warrants the original purchaser that for a period of two years
FA-262 Installation & Operator’s Manual42Out of Warranty Repairs Mircom Technologies Ltd. will at its option repair or replace out-of-warranty pro
FA-262 Installation & Operator’s ManualiiiList of FiguresFigure 1: FA-262 cabinet with door closed ...
Canada25 Interchange WayVaughan, ON L4K 5W3Tel: 905-660-4655 Fax: 905-660-4113© Mircom 2007Printed in CanadaSubject to change without prior noticewww.
FA-262 Installation & Operator’s Manual11.0 Introduction1.1 The FA-262 Fire Alarm Control UnitGeneral features•Two initiating device circuits, cla
FA-262 Installation & Operator’s Manual21.3 Technical Support and General InformationFor technical support call 1-888-660-4655, or email techsuppo
FA-262 Installation & Operator’s Manual32.0 Preparing to Install the FA-262 Fire Panel2.1 Unpacking the FA-262The basic FA-262 package includes th