The Buzzer and LED Indicators
4
Walk Test LED
CPU Fail LED
Auxiliary Disconnect LED
Signal Silence LED
Battery Trouble LED
Ground Fault LED
System Reset LED
The amber Walk Test indicator illuminates steadily to indicate that the panel is in walk test mode. If
the panel is left in this mode for over an hour with no operator activity, the panel will return to normal
and the Walk Test indicator will turn OFF.
The CPU Fail LED flashes amber at the trouble flash rate to indicate a microprocessor failure on the
main board.
The amber Auxiliary Disconnect LED flashes at the trouble rate when the Auxiliary Disconnect
button is pressed. It turns off when the Auxiliary Disconnect button is pressed a second time. When
on, the Auxiliary Disconnect LED signifies that auxiliary alarm relay and relay adder modules (if
disconnect is enabled) are not activated. If installed and enabled, the city tie module and the smart
relay annunciator relays are also inactive.
The Signal Silence indicator flashes amber at the trouble rate when indicating circuits are silenced
either by the Signal Silence button or by the Auto Signal Silence timer. It turns off when the signals
are re-sounded by a subsequent alarm or when the panel is reset.
The amber Battery Trouble LED flashes at the trouble rate when the battery is either low or
disconnected.
The amber Ground Fault LED flashes at the trouble rate when the ground fault detector detects a
ground fault on any field wiring. It turns off when the ground fault is cleared.
The amber System Reset LED illuminates for a short time when the System Reset button is
pressed.
WALK
TEST
CPU FAIL
AUX
DISCONNECT
SIGNAL
SILENCE
BATTERY
TROUBLE
GROUND
FAULT
SYSTEM
RESET