INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specications and models and also to discontinue models.
Description
Mircom’s FleX-Net
TM
Series Network Fire Alarm
Control Panels offer modular components to meet
a wide variety of applications. Designed for peer-
to-peer network communications, the FleX-Net
TM
Series allows for a maximum of 63 nodes, while
providing reliability, flexibility and expandability.
The FleX-Net
TM
Series is based on the proven and reliable
FX-2000 Series platform. Each base panel consists
of one intelligent signaling line circuit (SLC) capable
of supporting 99 analog sensors and 99 addressable
modules. In additon the base panel also consists of
4 Class A/B (Style Z/Y) Indicating Circuits rated at 1.7
Amps each and a large 4 x 20 back-lit alphanumeric
LCD display.
The audio control provides a multi-channel distributed
audio system that allows for efficient emergency
paging, evacuation signaling and reghters telephone
communication. Each audio card cage supports a
maximum of 4 QAA style ampliers for a maximum of
180 watts per cabinet.
The FleX-Net
TM
Series network conguration allows
the control panel to be connected to a Mircom network
to provide additional input circuits, visual zones,
programmable notication appliance circuits, and relays.
Each panel can be congured using standard FX-2000
components. The network interface module allows the
panels to communicate on a peer-to-peer network.
The network capabilities allow site specic customization
and the ability to meet local and national requirements.
Features
Fire Alarm Control
One expandable to ve Intelligent Signaling Line
Circuit (SLC)
Modular design
Each SLC is capable of supporting 99 Analog Sensors
and 99 Addressable Modules which can be wired in
Class A (Style 6 or 7) or Class B (Style 4)
Four Class A/B (Style Z/Y) Indicating Circuits rated at
1.7 Amps each
Large 4 by 20 character Back-lit LCD Display with user
friendly menu
Correlatable Switch Inputs which allows for multi-
functional outputs
Four Alarm Queues with selector switches and LEDs
for Alarm, Supervisory, Monitor and Trouble
Auxiliary relay contacts for Common Alarm, Common
Supervisory and Common Trouble
RS-232 output for remote system printer or CRT
Two Event History Logs comprised of a 1000 Alarm
History Log for alarm related events and a 2000 Event
Log for all events
Front Panel Auto-Congure and/or Computer laptop
Programmable
16 zone congurable LED annunciator complete with
individual slide-in labels for zone denition
Congurable for Coded Operation
Panel selection for Canadian (ULC) or U.S.A. (UL)
requirements for smoke sensors (sensitivity) via
computer laptop
Capability to adjust Intelligent Smoke Detector
sensitivity levels
Audio Control
Multi-channel operation
Distributed audio
5 reghter telephone channels
25 or 70 volt system
Multiple amplier sizes
Max. of 180 watts per Integrated Fire & Audio panel
Network Features
Up to 63 nodes
Peer-to-peer network communications
Multiple Lobby Control Centers
Class B (Style 4) or Class A (Style 6 or 7) wiring
conguration
Proprietary Arcnet Network Communications protocol
Supports copper and/or ber optic network cable
5940
NOT TO BE USED FOR INSTALLATION PURPOSES.
S7010
S7010
CATALOG NUMBER
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - CATALOG NUMBER

INTELLIGENT FIRE ALARM AND AUDIO NETWORK SYSTEM Mircom reserves the right to make changes at any time without notice in prices, colours, materials, co

Page 2 - FleX-Net

NOT TO BE USED FOR INSTALLATION PURPOSES.CAT. 5940page 2 of 8ECX-0012 Expander Chassis The ECX-0012 Expander Chassis for the FX-2009-12N supports up t

Page 3 - Adder Auxiliary Modules

NOT TO BE USED FOR INSTALLATION PURPOSES.CAT. 5940page 3 of 8Adder Hardwire ModulesDM-1008A Eight Initiating Circuit ModuleThe DM-1008A provides 8 Cla

Page 4 - Enclosures

NOT TO BE USED FOR INSTALLATION PURPOSES.CAT. 5940page 4 of 8RAX-1048TZ Programmable LED Annunciator ModuleThe RAX-1048TZ Programmable LED Annun

Page 5 - Paging Control Modules

NOT TO BE USED FOR INSTALLATION PURPOSES.CAT. 5940page 5 of 8ANC-5000 Audio Network Controller ModuleThe ANC-5000 provides audio microphone control on

Page 6 - Audio Ampliers

CAT. 5940page 6 of 8NOT TO BE USED FOR INSTALLATION PURPOSES.QAA-5415-70 and QAA-5415-25 Quad 15 Watt AmpliersThe QAA-5415-70 and QAA-5415-25 consi

Page 7 - Typical FleX-Net

CAT. 5940page 7 of 8NOT TO BE USED FOR INSTALLATION PURPOSES.Node 1 - Central Alarm & Control FacilityFX-2009-12N in a BB-5014RRAXN-LCD in a BB-10

Page 8 - Ordering Information

Canada25 Interchange WayVaughan, Ontario L4K 5W3Telephone: (905) 660-4655Fax: (905) 660-4113Web page: http://www.mircom.com Email: mail@mir

Comments to this Manuals