Adder Hardwire Modules
DM-1008A Eight Initiating Circuit Module
The DM-1008A provides 8 Class B (Style B) or 4 Class
A (Style D) Initiating Circuits congurable for Alarm,
Supervisory or Trouble zones. The DM-1008A occupies
one module slot in the FX-2009-12N main chassis.
SGM-1004A Four Indicating Circuit Module
The SGM-1004A provides 4 Class A/B (Style Z/Y)
Notification Appliance Circuits configurable as
Silenceable or Non-Silenceable. Each NAC circuit
is rated at 1.7 Amps. Each of the NAC circuits have
individual signal silence inputs which are jumper
selectable. The SGM-1004A occupies one module
slot in the FX-2009-12N main chassis.
ALCN-396S Dual Analog Loop Controller Module
The ALCN-396S Dual Analog Loop Controller Module
provides two additional Signaling Line Circuits (SLC) to
the FX-2003-12N consisting of 99 Analog Sensors and 99
Addressable Modules per loop. The ALCN-396S occupies
one module slot in the FX-2009-12N main chassis.
Adder Loop Controller Modules
Adder Auxiliary Modules
PR-300 Polarity Reversal/City Tie Module
The PR-300 Polarity Reversal/City Tie Module provides
the system with a supervised City Tie (24 VDC/200 mA
max.) and Polarity Reversal connection (24 VDC (open
circuit), 8 mA max. (shorted)). The PR-300 occupies
one module slot in the FX-2009-12N main chassis.
UDACT-300A Digital Alarm Communicator Module
The UDACT-300A Digital Alarm Communicator Module
allows the FX-2003-12N to transmit addressable point
information to a central station. The UDACT-300A occupies
one module slot in the FX-2009-12N main chassis.
RM-1008A Eight Relay Circuit Module
The RM-1008A provides the FX-2003-12N with eight
individual congurable relays per module. Each relay
provides one Form C contact rated at 28 VDC @1 Amp
(resistive load) as well as a Green LED to indicate
that the relay is active. The RM-1008A occupies one
module slot in the FX-2003-12N main chassis.
FNC-2000 Fire Network Controller Module
The FNC-2000 provides network capability to the FX-2009-
12N. One Fire Network Controller Module is required per
network node panel. In addition the FNC-2000 provides
an interface for adding an optional FOM-2000-SP Fiber
Optic Network Adder Module. The FNC-2000 mounts in
the FX-2009-12N main chassis.
Fire Network Controller Modules
FOM-2000-SP Fiber Optic Network Adder Module
The FOM-2000-SP Fiber Optic Network Adder Module
allows for the use of ber optic cabling on the FX-2009-
12N. It seamlessly connects to the interface on the FNC-
2000 Fire Alarm Network Controller Module.