RAX-1048TZDS Programmable LED Annunciator
Module
The RAX-1048TZDS Programmable LED Annunciator
Module provides 48 programmable bi-colored LEDs. The
RAX-1048TZDS connects to the main panel or either the
RAXN-LCD or RAM-1032TZDS when mounted remotely.
The RAX-1048TZDS occupies one display position in the
BBX-FXMNS, BB-1000 or BB-5000 Series enclosures.
Remote LCD Annunciators
RAXN-LCD Remote LCD Annunciator
The RAXN-LCD Remote LCD Annunciator is equipped
with a 4 line x 20 character back-lit alphanumeric LCD
display that provides an exact replica of the main FleX-
Net re alarm control panel display. The RAXN-LCD
occupies one display position in the BBX-FXMNS,
BB-1000 or BB-5000 Series enclosures.
RAXN-LCDG Remote Graphic LCD Annunciator
The RAXN-LCDG Remote Graphic LCD Annunciator is
equipped with a 24 line x 40 character back-lit graphical LCD
display that is used to display 9 events per page. Each event
is displayed over 2 lines with 40 characters per line allowing
emergency information to be displayed in easy to read
format. The RAXN-LCDG occupies one display position in
the BBX-FXMNS, BB-1000 or BB-5000 Series enclosures.
Remote LED Annunciators
RAM-1032TZDS Main Remote LED Annunciator
The RAM-1032TZDS Main Remote LED Annunciator
provides common annunciator functions and 32 points of
LED annunciation. The RAM-1032TZDS has indicators for
A.C. On, Common Trouble and Signal Silence and controls
for System Reset, Lamp Test, Fire Drill, Buzzer Silence
and Signal Silence. The RAM-1032TZDS occupies one
display position in the BBX-FXMNS, BB-1000 or BB-5000
enclosures.
IPS-2424DS Programmable Input Switches
Module
The IPS-2424DS provides 24 programmable switches
that can be congured for ancillary functions such as zone
bypass or added common control functions. The IPS-
2424DS connects to the main panel or the RAXN-LCD
when mounted remotely. The IPS-2424DS occupies one
display position in the BBX-FXMNS, BB-1000 or BB-5000
Series enclosures.
FDX-008 Fan Damper Control Module
The FDX-008 Fan Damper Control Module provides
individually programmed circuits which can be used for fan
or damper control. The FDX-008 connects to the main panel
or the RAXN-LCD and occupies one display position in the
BBX-FXMNS, BB-1000 or BB-5000 Series enclosures.