RAM-300LCD Installation and Operation Manual
7
Specifications & Features
Enclosure
Enclosure may be mounted on a 4” square electrical box or on a wall.
Electrical Specifications
24 VDC nominal voltage
LCD Display, Pushbutton Controls and LED indicators.
Local Buzzer, Indicators (AC-On, Alarm, Supervisory, Trouble and CPU Fail), and Controls (System Reset,
Signal Silence, Fire Drill, Buzzer Silence and Lamp Test,).
Annunciation of up to 16 Points.
Not Expandable.
Standby 16 mA Max., Alarm 40mA Max. All LEDs illuminated 40 mA Max.
Current Drain for Battery Calculations
The maximum normal current drain will be during Lamp Test when all lamps are illuminated on one chassis at a
time. Thus the currents are:
Normal Standby =16 mA
Maximum =40 mA
The Normal Standby Current is used for battery size calculations (see the FA-300 Series or FX-350/351 Series
Fire Alarm Control Panel manual for battery calculations) and includes the current drain for the Trouble Buzzer,
Trouble LED, and one Alarm LED. The Maximum Current is used to calculate the wire size (see Wiring section
above).