Page view 7
Functional Setup
4
DIP Switches
There are two DIP switches to be set. SW30 is found at the bottom right corner of the board and is used to select
the annunciator address. Valid addresses are 1 to 6 inclusive for FA-300 Series, 1 to 7 for FX-350/351. Set address
as follows:
RAM-300LCD Address DIP Switch Setup
DIP switch SW31 is found at the bottom left hand corner and is used to select a number of features. DIP switch
SW31 is set as follows:
Address SW30-1 SW30-2 SW30-3
1ONOFFOFF
2OFFONOFF
3ONONOFF
4OFFOFFON
5ONOFFON
6 OFF ON ON
7 (FX-350/351) ON ON ON
Note: SW30-4 DIP switch is not used.
Note: For the FX-350/351 Series Fire Alarm Panels, if the number of annunciators programmed is 5, then
the first five addresses (1 to 5 inclusive) must be assigned to the RAM-300LCD annunciators.
DIP Switch SW31 Position Function
1 ON Disable System Reset Button
1 OFF Enable System Reset Button
2 ON Disable Signal Silence Button
2 OFF Enable Signal Silence Button
3 ON Disable Fire Drill Button
3 OFF Enable Fire Drill Button
4 ON Disable Lamp Test Button
4 OFF Enable Lamp Test Button
5 ON Disable Buzzer Silence Button
5 OFF Enable Buzzer Silence Button
6 NOT USED
7 ON 16 bit checksum (for FX-350/351 panels)
7 OFF 8 bit checksum (for FA-300 Series panels)
8 NOT USED