RAM-300LCD Installation and Operation Manual
1
Introduction
The RAM-300LCD is a remote annunciator used for the FA-300 Series and FX-350/351 Series Fire Alarm Panels. It
provides remote access to the fire alarm panel.
The RAM-300LCD has an LCD display, common feature LEDs and pushbuttons, as well as an alpha numeric
keypad for the LCD.
The RAM-300LCD comes complete with an enclosure and can be surface mounted.
Each RAM-300LCD has its own address. Addresses available are 1 to and including 7. The buttons on the left side
may be individually disabled if required, by setting DIP Switch SW31, see Functional Setup section following.
This annunciator may be selected to operate as an ancillary device using DIP Switch SW31-6 to disable all buttons
except, Lamp Test, Buzzer Silence, Info and Arrow Buttons.
Note: Configuration of the FA-300 Series and FX-350/351 Series fire alarm panels from this remote
annunciator is not allowed.
Note: This ancillary device option, if selected takes priority over any other selections made on DIP Switch
SW31.
FA-300 SERIES
Remote Annunciator
SYSTEM
RESET
SIGNAL
SILENCE
FI R E
DRIL L
BUZZER
SILENCE
LAM P
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
ME N U
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
7.2"
7.7"
1.25"
Page view 4
1 2 3 4 5 6 7 8 9 10 ... 19 20

Comments to this Manuals

No comments