Appendix D: Alarm Verification Timing
132
ANC-5000 Board with Ethernet Port, Address Setting (DIP SWITCH SW1)
ANC-5000 Board without Ethernet Port, Address Setting (DIP SWITCH SW1)
ACN-792M Loop Adder Module (CPU) Address Setting (DIP SWITCH SW1)
RAXN-LCD/RAXN-LCDG Remote Annunciator Address Setting (DIP SWITCH SW1)
Appendix D: Alarm Verification Timing
A Manual Station, or other contact-closure device, would remain shorted and be detected during the very short
Zone Power burst within the first three seconds. A Smoke Detector will have been reset, and will require some
minimum time to power-up, thus the Verification cycle will be entered.
ANC-5000
ADDR SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8
1 OFFOFFOFFOFFOFFOFFOFF ON
2 OFF OFF OFF OFF OFF OFF ON OFF
3 OFF OFF OFF OFF OFF OFF ON ON
4 OFFOFFOFFOFFOFF ON OFFOFF
5 OFF OFF OFF OFF OFF ON OFF ON
6 OFF OFF OFF OFF OFF ON ON OFF
7 OFF OFF OFF OFF OFF ON ON ON
ANC-5000
ADDR SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8
1ONOFFOFF
Leave in "OFF" position as Factory Set.
2OFFONOFF
3ONONOFF
4OFFOFFON
5ONOFFON
6OFFONON
7 ONONON
ALCN-792M
ADDR SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8
1 ON OFFOFFOFFOFFOFFOFF
Put in "ON" position for
firmware restore to defaults
during power up. At all other
times put in "OFF" state.
2 OFF ON OFF OFF OFF OFF OFF
3 ON ON OFF OFF OFF OFF OFF
4 OFF OFF ON OFF OFF OFF OFF
5 ON OFF ON OFF OFF OFF OFF
6 OFF ON ON OFF OFF OFF OFF
7 ONONONOFFOFFOFFOFF
RAXN-LCD/G
ADDR SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 SW1-7 SW1-8
33 ON OFF OFF OFF OFF ON
Leave in "OFF"
position as
Factory Set.
34 OFF ON OFF OFF OFF ON
35 ON ON OFF OFF OFF ON
36 OFF OFF ON OFF OFF ON
37 ON OFF ON OFF OFF ON
38 OFFON ONOFFOFFON
39 ON ON ON OFF OFF ON
SMOKE DETECTOR
IN ALARM
3s 1s 10s
(30s) (65s)
ULI/ULC Retard / Reset / Restart
60 seconds Maximum
Reset
Restart
ULI/ULC Conrmation Period
60 seconds Minimum
These intervals are determined
by the maximum Detector Reset
time, which is 1s for our uses.
This interval is determined by the maximum
Detector Start-up time. ULC states a maximum hold
time of 30 seconds.