Mircom QMT-5302 Specifications Page 64

  • Download
  • Add to my manuals
  • Print
  • Page
    / 152
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 63
Field Wiring
60
Power Supply Connections
The power supply is part of the main chassis. The ratings are outlined in the table below.
See Appendix A for more power supply specifications. Wire as shown below with proper gauge wire.
Figure 45: Power Supply Connections
Model Electrical Input Ratings
Power Supply
Total Current
Battery Fuse on Main
Module
FX-2003-12N/DS & FX-2017-
12N/DS Main Chassis
120 VAC, 60 Hz, 2A /
240VAC, 50hz, 1A
12 amps maximum
20 Amp, 1-1/4" Slow Blow
Non-replaceable Fuse
FX-2009-12N/DS Main
Chassis
120 VAC, 60 Hz, 2A /
240VAC, 50hz, 1A
12 amps maximum
20 Amp, 1-1/4" Slow Blow
Non-replaceable Fuse
All Chassis’ IN-LINE 20 Amp, 1 1/4” Fast Acting Fuse, positive side of Battery Connection
CAUTION:
To prevent sparking, connect batteries after the system’s main A.C. power is turned ON.
Do not exceed power supply ratings.
Adhere to voltage markings as specified on labels.
P13
CONNECT GREEN
EARTH GROUND WIRE
TO MAIN MODULE PCB
MOUNTING SCREW.
N
G
GREEN
TO 24 VDC
BATTERY
BLACK
P11
P10
P12
+
BAT
RED
TO DEDICATED
BRANCH CIRCUIT
L
L
20 Amp, 1 1/4” IN-LINE
FAST ACTING FUSE
20 Amp, 1 1/4” SLOW
BLOW FUSE
FUSE
GND
Page view 63