FA-300 Series LCD Version Installation and Operation Manual
13
DIP Switch and Jumper Selections for Main Board and Adder
Modules
Main Fire Alarm Board
Figure 5: Main Fire Alarm Board DIP switch and jumper settings for FA-301 LCD Panels
S-+NC NOCNC NOCNC NOCNC NOC
+-+-
COM(+)
CO M (-)
TR LTRB RTRT RTRT
RES CO RES CO
LINE1LINE2
JW3
JW2
JW1
-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DET 5DET 6DET 7DET 8DET 9DET 1 0DET 11DET 12SIG 1SIG 2SIG 3SIG 4
JW6
JW5
JW4
TO PR-300 MODULE
TO RM-312/RM-306 RELAY MOD ULE
RS-485AUX. RELAYAL ARM R EL A Y
SUPERVISORY
RELAY
TROU BLE
RELAY
AUX
SUPPLY
4-WIRE
SUPPLY
UN FILTERED
RTI
PORT
P1 P 2P3 P4
+
_
BATTERY SEC. TX
Telephone line
#1
Telephone line
#2
RS-485 for
annunciators
Auxiliary Relay
Alarm Relay
Supervisory Relay
Trouble Relay
Auxiliary Supply
4-wire Supply
Unfiltered 24V
supply
connect to Remote
trouble indicator
Initiating zone 1 TO 12
Indicating zone 1 TO 4
Connect to RM-312/
RM306 Relay
module
Connect to PR-300
To Battery To secondary of AC
transformer
JW2 - ON- when
RM312/RM306 not
connected
JW1 - ON- when
PR-300 not connected
JW3- Removed all the time
JW6 -Open all the time
JW5 -Normally Open
SYSTEM
RES ET
SIGNAL
SILEN CE
FIRE
DRILL
BUZZER
SILEN CE
LAMP
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MENU
CAN CEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A .C. ON AL ARM S UPV TRBL CPU F AIL
SYSTEM NORMAL
18:01 MON 2003-04-05
JW4 -Normally Open
JW7
JW7- Normally Open
For PC programming use UIMA
interface module not UL-864 or
ULC-S527 listed. Please refer to
Document LT-929 for details