Mircom FA-300 Series Installation Manual Page 40

  • Download
  • Add to my manuals
  • Print
  • Page
    / 84
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 39
Indicators, Controls and Operations
32
either manually or automatically. While sounding, these devices follow the pattern appropriate for the condition: the
configured Evacuation Code (default is Temporal Code) during alarm.
Non-Silenceable Signal
The Non-Silenceable Signal Circuit is used for audible devices such as bells and piezo mini-horns that may not be
silenced either manually or automatically. While sounding, these devices follow the pattern appropriate for the
condition: the configured Evacuation Code (default is Temporal Code) during alarm.
Silenceable Strobe
Silenceable strobes will be silenced when the “signal silence” key is pressed. For synchronous strobes see
supported protocol/devices section. (NB: Strobes do not support any code pattern.)
Non-Silenceable Strobes
Non-Silenceable Strobes will not be silenced when the “signal silence” key is pressed. For synchronous strobes see
supported protocol/devices section. (NB: Strobes do not support any code pattern.)
Evacuation codes
Continuous On 100% of the time
Temporal Code 3 of 0.5 second on, 0.5 second off then, 1.5 second pause
March Code 0.5 second on, 0.5 second off
California Code 5 seconds on, 10 seconds off
Figure 24: Evacuation Codes
0.5s
0
.
5
s
1.5s
0.5s
0
.
5
s
5s 10s
CONTIN OU S
TEMPORA L CODE
MARCH CODE
CA L IFORNIA COD E
0.5s
0
.
5
s
1.5s
0.5s
0
.
5
s
5s 10s
CONTIN OU S
TEM PORAL CODE
MARCH CODE
CA LIF OR NIA CO D E