FA-300 Series LCD Version Installation and Operation Manual
19
Field wiring
Main Fire Alarm Board Field Wiring
Wire devices to the terminals as shown in the figures that follow. Refer to the Wiring Tables for wire gauges and to
Appendix A for specifications.
Initiating Circuit Wiring
Wiring diagrams for the initiating circuits are shown below. The panel supports Style B wiring for the initiating circuits
and Style D wiring for the indicating circuits. The initiating circuits are supervised by a 3.9K End-of-Line Resistor or
for power saving an Active-End-of-Line.
Figure 13: Initiating circuit – Class B or Style B wiring
CAUTION: Do not exceed power supply ratings.
Note: According to Configuration, End-of-Line Resistors on initiating circuits must be all 3.9K ohms or all
Active End-of-Line resistors.
+
-
STYLE B
WIRING
STYLE B
WIRING
INITIATING
CIRCUIT #1
INITIATING
CIRCUIT #2
INITIATING
CIRCUIT - 1
ALARM ZONE
INITIATING
CIRCUIT - 2
SUPERVISORY
ZONE
ION SMOKE
DETECTOR
PHOTO SMOKE
DETECTOR
HEAT
DETECTOR
PULL STATION
3.9K 1/2 WATT ELR
SUPERVISORY
NOTE: ACTIVE END OF LINE
RESISTORS MAY BE USED, BUT
THEY MUST BE USED ON ALL
THE INITIATING CIRCUITS.
FIRE ALARM MAIN BOARD
+
-
DET 1DET 2