FA-300 Series LCD Version Installation and Operation Manual
37
Command Menu
The main command menu is pictured below. The first line of the LCD will always show
“-Command Menu-“, and the second line scrolls through different selections. Use the “UP” and “DOWN” keys to
scroll through the menu, and press the “ENTER” key to make a selection. To exit from the main command menu,
select the “Exit” menu option and then press either the “CANCEL” or “ENTER” key.
Pressing “LAMP TEST” at any time will show information about the system and the software version as shown
below. It will also illuminate all the LEDs across the top of the display except for the CPU Fail LED.
The first line shows the model number and panel type and the second line shows the software version number. The
version of the software is read as Major.Minor.Revision.
Note: Command Menu features 1 and 9 can only be accessed if jumper JW5 is placed on the main board,
see Table 1.
-Command Menu-
1. FA-300 Config
2. Config Info
3. Set Time
4. Set Password
5. View EventLog
6. Clear EventLog
7. Walk Test
8. I3 Loop test
9. Dialer Config
10.Test Dialer
11.Bypass Det Ckt
12.Bypass NAC Ckt
13.Aux Disc
14.Exit
FA-301-12DDR wUDACT
Version 0.0.4
Page view 44