DIP Switch and Jumper Selections for Main Board and Adder Modules
14
Figure 6: Main Fire Alarm Board DIP switch and jumper settings for FA-300 LCD
Panels
Table 1: Connectors and Jumpers on the Main Fire Alarm Board
P5 Cable from P1 of the PR-300 Polarity Reversal and City Tie Module connects here. Otherwise not used.
P6
Cable from connector P1 of the RM-312 or RM-306 Relay Adder Module connects here. Otherwise not
used.
JW1
On the Main Fire Alarm Module, this jumper must be removed if a PR-300 Polarity Reversal and City Tie
Module is installed.
JW2
Remove this jumper if a RM-312 or RM-306 Relay Adder Module is used.
JW3 Removed all the time.
JW4
Normally open. Place jumper here and power down (AC and Batteries) then power back to revert to default
password. After reset remove the jumper. Leave normally open.
JW5
Normally open to BLOCK remote configuration via modem, PC with a UIMA converter module or using the
LCD and keys at the panel. Place jumper here to ALLOW any type of configuration.
JW6 Not used, open (not available on FA-300 LCD panels).
JW7 Not used, open.
S-+NC NOCNC NOCNC NOCNC NOC
CO M(+ )
CO M (-)
TRLTRB
RTRT RTRT
RES CO RES CO
LINE1LINE2
JW2
JW 1
-+-+-+-+-+-+-+-+-+-+
DET 1DET 2DET 3DET 4DET 5DET 6
SIG 1SIG 2
TO PR-300 MODULE TO RM-312/RM-306 RELAY MODULE
RS-485AUX. RELAYAL ARM R EL A Y
SUPERVISORY
RELAY
TROU BLE
RELAY
AUX
SUPPLY
4-WIRE
SUPPLY
UN FILTERED
RT I
PO RT
P1 P 2P3 P4
+
_
BATTERY SEC. TX
Telephone line
#1
Telephone line
#2
RS-485 for
annunciators
Auxiliary Relay
Alarm Relay
Supervisory Relay
Trouble Relay
Initiating zone 1 TO 6
To Battery To secondary of AC
transformer
JW2 - ON- when
RM312/RM306 not
connected
JW1 - ON- when
PR-300 not connected
SYSTEM
RES ET
SIGNAL
SILENCE
FIRE
DRILL
BUZZER
SILENCE
LAMP
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MENU
CAN CEL
INFO
ABC DEF
GHI JKL MNO
PRS
TUV
WXY
QZ
A.C. ON ALARM SUPV TRBL CPU FAIL
SYSTEM NORMAL
18:01 MON 2003-04-05
AUX
SUPPLY
P5 P6
JW 3
JW3
Removed all
the time
JW4
JW5
JW7
JW7
Normally open
JW4 - Normally Open
JW5 - Normally Open
For PC programming use UIMA
interface module not UL-864 or
ULC-S527 listed. Please refer to
Document LT-929 for details
Signal Circuit -1
Signal Circuit -2
Auxiliary
Supply
4-wire Supply
Unfiltered 24V
supply
Connect to
Remote Trouble
Indicator
Page view 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 83 84

Comments to this Manuals

No comments

Humanscale Monitory podręczniki użytkownika

Zaczynanie od M

Kliknij na poniższy alfabet, aby przejść do pełnej listy modeli zaczynających się od tej litery

Modele Rodzaj dokumentu
M2 Hang Tag
Instrukcja Użytkownika   Humanscale M2 Hang Tag User Manual, 5 strony
M8 Conversion to and from Crossbar
Instrukcja Użytkownika   Humanscale M8 Conversion to and from Crossbar User Manual, 1 strony
M8 Installation
Instrukcja Użytkownika   Humanscale M8 Installation User Manual, 2 strony
MFlex
Instrukcja Użytkownika   Humanscale MFlex User Manual, 2 strony