FA-300 Series LCD Version Installation and Operation Manual
47
3. Set Time (Command-Menu)
Note: Refer to How to Use the Keypad to Program the FA-300 on page 39 for detailed instructions on
making menu selections.
Command Menu/Set Time
1. Daylight saving time
[X] DISABLE ->Default
[ ] ENABLE
Use this function to enable
daylight savings time.
Command Menu/Time Clock
2. Set time and date
Default
00:00 MON 2000-01-01
Use this function to set the time
and date. Use the “LEFT” and
“RIGHT” keys to move the
cursor to the desired location in
the display and use the “UP”
and “DOWN” keys to increase
or decrease the values. Press
the “ENTER” key to accept the
changes and the “CANCEL”
key to ignore the changes.
Note: time is in 24hr format
Command Menu/Time Clock
3. Compensation
Once the compensation value is entered
the display will be:
Compensation value
can range from -15 to
+15 seconds.
Use the up down arrow keys to
select daily compensation
value and press ENTER. For a
fast clock adjust negatively. For
a slow clock adjust positively.
For example: for a clock which
runs 5 minutes a month (based
on 30 days) fast select -10
seconds.
1 Daylight Save
2 Time Clock
3 Compensation
Daylight Saving
[X] DISABLE
HH:MM WKD YYYY-MM-DD
00:00 MON 2000-01-01
Daily Compensation:
0
Daily Compensation:
Panel Config Updated